Firmware Manual

9000X AF Drives
MN04004001E
For more information visit: www.eaton.com
6-23
August 2010
Multi-Purpose Control Application
Table 6-24: Protections — G1.7 (Continued)
Code Parameter Min. Max. Unit Default Cust ID Note
P1.7.16 Stall frequency limit 1.0 Par. 1.1.2 Hz 25.0 712
P1.7.17 Underload
protection
0 3 0 713 0 = No response
1 = Warning
2 = Fault.stop acc. to 1.4.7
3 = Fault.stop by coasting
P1.7.18 Field weakening
area load
10.0 150.0 % 50.0 714
P1.7.19 Zero frequency load 5.0 150.0 % 10.0 715
P1.7.20 Underload
protection time
limit
2.00 600.00 s 20.00 716
P1.7.21 Response to
thermistor fault
0 3 2 732 0 = No response
1 = Warning
2 = Fault.stop acc. to 1.4.7
3 = Fault.stop by coasting
P1.7.22 Response to
fieldbus fault
0 3 2 733 See P1.7.21
P1.7.23 Response to slot
fault
0 3 2 734 See P1.7.21
P1.7.24
No. of PT100 inputs
03 0 739
P1.7.25 Response to PT100
fault
0 3 0 740 0 = No response
1 = Warning
2 = Fault.stop acc. to 1.4.7
3 = Fault.stop by coasting
P1.7.26 PT100 warning limit -30.0 200.0 120.0 741
P1.7.27 PT100 fault limit -30.0 200.0 130.0 742
P1.7.28 PT100 Numbers 2 0 3 0 743
P1.7.29 PT100 Flt Resp 2 0 3 0/No
Action
744 See External Fault
P1.7.30 PT100WarnLimit2 -30 200 °C 120 745
P1.7.31 PT100 FltLimit 2 -30 200 °C 130 746
P1.7.32 FB WatchdogDelay 0 10.00 s 0 1354 0 = Not monitored
P1.7.33 FCW monitor bit 0 1 1 / Fault
High
771
P1.7.34 FB monitor delay 0 10.00 s 0 772 0 = Not monitored
P1.7.35 Ref fault select 0 4 1 / AI2 770 0 = AI1
1 = AI2
2 = AI3
3 = AI4
4 = Fieldbus
SPX Only
P1.7.36 SafeDisable Mode 1 2 1/
Warning
755 1 = Warning
2 = Fault