Firmware Manual
9000X AF Drives
6-20 For more information visit: www.eaton.com
MN04004001E
August 2010
Multi-Purpose Control Application
Skip Frequency Parameters (Control Keypad: Menu M1
➔
G1.5)
Table 6-22: Skip Frequency Parameters — G1.5
Motor Control Parameters (Control Keypad: Menu M1
➔
G1.6)
Table 6-23: Motor Control Parameters — G1.6
Code Parameter Min. Max. Unit Default Cust ID Note
P1.5.1 Skip frequency
range 1 low limit
0.00 Par. 1.5.2 Hz 0.00 509
P1.5.2 Skip frequency
range 1 high limit
0.00 Par. 1.1.2 Hz 0.00 510 0 = Skip frequency range 1
not used
P1.5.3 Skip frequency
range 2 low limit
0.00 Par. 1.5.4 Hz 0.00 511
P1.5.4 Skip frequency
range 2 high limit
0.00 Par. 1.1.2 Hz 0.00 512 0 = Skip frequency range 2
not used
P1.5.5 Skip frequency
range 3 low limit
0.00 Par. 1.5.6 Hz 0.00 513
P1.5.6 Skip frequency
range 3 high limit
0.00 Par. 1.1.2 Hz 0.00 514 0 = Skip frequency range 3
not used
P1.5.7 Skip frequency
acc./dec. ramp
0.1 10.0 Times 1.0 518
Code Parameter Min. Max. Unit Default Cust ID Note
P1.6.1
Motor control mode 0 4 0 600 SVX:
0 = Freq Control
1 = OL SpeedCont
2 = OL Torq Ctrl
SPX Only
3 = CL SpeedCont
4 = CL Torq Ctrl
P1.6.2
V/Hz Boost 0 1 0 109 0 = Not used
1 = Automatic torque boost
P1.6.3
V/Hz Ratio Select 0 3 0 108 0 = Linear
1 = Squared
2 = Programmable
3 = Linear with flux optim.
P1.6.4
Field weakening point 8.00 650 Hz 60.00 602
P1.6.5
Voltage at field
weakening point
10.00 200.00 % 100.00 603 n% x U
nmot
P1.6.6
V/Hz curve midpoint
frequency
0.00 650 Hz 60.00 604
P1.6.7
V/Hz curve midpoint
voltage
0.00 100.00 % 100.00 605 n% x U
nmot
Parameter max. value = par. 1.6.5
P1.6.8
Output voltage at zero
frequency
0.00 40.00 % 1.30 606 n% x U
nmot