Table 6-17: Limit Settings — G1.3.4 (Continued)
Analog Output 1 (Control Keypad: Menu M1
➔
G1.3.5)
Table 6-18: Analog Output 1 Parameters — G1.3.5
Code Parameter Min. Max. Unit Default Cust ID Note
P1.3.4.13 Ain Supv Input 0 4 0 356 0 = Not used
1 = AI1
2 = AI2
3 = AI3
4 = AI4
P1.3.4.14 Ain Supv Llim 0 Par. 1.3.4.15 % 10.00 357
P1.3.4.15 Ain Supv Hlim Par. 1.3.4.14 100.00 % 90.00 358
Code Parameter Min. Max. Unit Default Cust ID Note
P1.3.5.1 Analog output 1
signal selection
AnOUT:0.1 AnOUT:E.10 A.1 464
P1.3.5.2 Analog output 1
function
0 15 1 307 0 = Not used
1 = Output freq. (0 – f
max
)
2 = Freq. reference (0 – f
max
)
3 = Motor speed (0 – Motor
nominal speed)
4 = Motor current (0 – I
nMotor
)
5 = Motor torque (0 – T
nMotor
)
6 = Motor power (0 – P
nMotor
)
7 = Motor voltage (0 – U
nMotor
)
8 = DC-Bus volt (0 – 1000V)
9 = AI1
10 = AI2
11 = Output freq. (f
min
- f
max
)
12 = Motor torque
(–2…+2xT
Nmot
)
13 = Motor power
(–2…+2xT
Nmot
)
14 = PT100 temperature
15 = FB Data In 4
P1.3.5.3 Analog output 1
filter time
0.00 10.00 s 1.00 308 0 = No filtering
P1.3.5.4 Analog output 1
inversion
0 1 0 309 0 = Not inverted
1 = Inverted
P1.3.5.5 Analog output 1
minimum
0 1 0 310 0 = 0 mA
1 = 4 mA
P1.3.5.6 Analog output 1
scale
10 1000 % 100 311
P1.3.5.7 Analog output 1
offset
-100.00 100.00 % 0.00 375