Firmware Manual

9000X AF Drives
MN04004001E
For more information visit: www.eaton.com
6-13
August 2010
Multi-Purpose Control Application
Digital Inputs (Control Keypad: Menu M1
G1.2.7)
Table 6-13: Digital Input Signals — G1.2.7
cc = closing contact; oc = opening contact.
Code Parameter Min. Max Default ID Note
P1.2.7.1
Start Signal 1 DigIN:0.1 DigIN:E.10 DigIN:A.1 403 See P1.2.1.1
P1.2.7.2
Start signal 2 DigIN:0.1 DigIN:E.10 DigIN:A.2 404 See P1.2.1.1
P1.2.7.3
Run Enable DigIN:0.1 DigIN:E.10 DigIN:0.2 407 Motor start enabled (cc)
P1.2.7.4
Reverse DigIN:0.1 DigIN:E.10 DigIN:0.1 412 Direction forward (oc)
Direction reverse (cc)
P1.2.7.5
Preset Speed 1 DigIN:0.1 DigIN:E.10 DigIN:0.1 419 See preset speeds in Basic
Parameters (G2.1)
P1.2.7.6
Preset Speed 2 DigIN:0.1 DigIN:E.10 DigIN:0.1 420
P1.2.7.7
Preset Speed 3 DigIN:0.1 DigIN:E.10 DigIN:0.1 421
P1.2.7.8
Mot Pot Down DigIN:0.1 DigIN:E.10 DigIN:0.1 417 Mot.pot. reference decreases (cc)
P1.2.7.9
Mot Pot Up DigIN:0.1 DigIN:E.10 DigIN:0.1 418 Mot.pot. reference increases (cc)
P1.2.7.10
Fault Reset DigIN:0.1 DigIN:E.10 DigIN:A.3 414 All faults reset (cc)
P1.2.7.11
External Fault (close) DigIN:0.1 DigIN:E.10 DigIN:A.5 405 Ext. fault (F51) displayed (cc)
P1.2.7.12
External Fault (open) DigIN:0.1 DigIN:E.10 DigIN:0.2 406 Ext. fault (F51) displayed (oc)
P1.2.7.13
Acc/Dec Time Sel DigIN:0.1 DigIN:E.10 DigIN:A.6 408 Acc/Dec time 1 (oc)
Acc/Dec time 2 (cc)
P1.2.7.14
Acc/Dec Prohibit DigIN:0.1 DigIN:E.10 DigIN:0.1 415 Acc/Dec prohibited (cc)
P1.2.7.15
DC Brake Command DigIN:0.1 DigIN:E.10 DigIN:0.1 416 DC braking active (cc)
P1.2.7.16
Jogging Speed DigIN:0.1 DigIN:E.10 DigIN:A.4 413 Jogging speed selected for
frequency reference (cc)
P1.2.7.17
AI1/AI2 Select DigIN:0.1 DigIN:E.10 DigIN:0.1 422 cc = AI2 is used as reference,
when ID117 = 14
P1.2.7.18
Force Remote DigIN:0.1 DigIN:E.10 DigIN:0.1 409 Force control place to Remote (cc)
P1.2.7.19
Parameter Set1/Set2 Sel DigIN:0.1 DigIN:E.10 DigIN:0.1 496 Closed cont. = Set 2 is used
Open cont. = Set 1 is used
P1.2.7.20
Motor Ctrl Mode 1/2 DigIN:0.1 DigIN:E.10 DigIN:0.1 164 Closed cont. = Mode 2 is used
Open cont. = Mode 1 is used
P1.2.7.21 CPX Temp Open DigIN:0.1 DigIN:E.10 DigIN:0.2 1686 CPX Temperature Fault