Firmware Manual
9000X AF Drives
6-12 For more information visit: www.eaton.com
MN04004001E
August 2010
Multi-Purpose Control Application
Analog Input 4 (Control Keypad: Menu M1
➔
G1.2.5)
Table 6-11: Analog Input 4 Parameters — G1.2.5
Free Analog Input Signal Selection (Keypad: Menu M1
➔
G1.2.6)
Table 6-12: Free Analog Input Signal Selection — G1.2.6
Code Parameter Min. Max. Unit Default Cust ID Note
P1.2.5.1
AI4 signal
selection
0 0.1 152
P1.2.5.2 AI4 filter time 0.00 10.00 s 0.10 153 0 = No filtering
P1.2.5.3 AI4 signal range 0 3 1 154 0 = 0–100%
1 = 4mA/20%–100%
2 = -10V...+10V
3 = Custom range
P1.2.5.4 AI4 custom
minimum setting
-160.00 160.00 % 0.00 155
P1.2.5.5 AI4 custom
maximum setting
-160.00 160.00 % 100.00 156
P1.2.5.6 AI4 signal
inversion
0 1 0 162 0 = Not inverted
1 = Inverted
Code Parameter Min. Max. Unit Default Cust ID Note
P1.2.6.1 Scaling of current
limit
0 5 0 399 0 = Not used
1 = AI1
2 = AI2
3 = AI3
4 = AI4
5 = Fieldbus
(FBProcessDataIN2)
P1.2.6.2 Scaling of DC-
braking current
0 5 0 400 See par. 1.2.6.1
P1.2.6.3 Reducing of acc./
dec. times
0 5 0 401 See par. 1.2.6.1
P1.2.6.4 Reducing of
torque supervision
limit
0 5 0 402 See par. 1.2.6.1
P1.2.6.5 Torque limit 0 5 0 485 See par. 1.2.6.1