Firmware Manual
9000X AF Drives
MN04004001E
For more information visit: www.eaton.com
6-9
August 2010
Multi-Purpose Control Application
Table 6-6: Basic Parameters — G1.1 (Continued)
Input Signals
Basic Settings (Control Keypad: Menu M1
➔
G1.2.1)
Table 6-7: Input Signals: Basic Settings — G1.2.1
Code Parameter Min. Max. Unit Default ID Note
P1.1.14 Remote reference 0 15 0/AI1 174 See par. 1.1.13
P1.1.15 Identification 0 1/2 0/No Action 631 0 = No Action
1 = ID No Run
SPX Only
2 = ID With Run
P1.1.16 V/Hz Boost 0 1 0/None 109 0 = None
1 = AutoTorqBoos
P1.1.17 Jog Speed Ref Min Freq Max Freq Hz 5.00 124
P1.1.18 Preset Speed 1 Min Freq Max Freq Hz 10.00 105
P1.1.19 Preset Speed 2 Min Freq Max Freq Hz 15.00 106
P1.1.20 Preset Speed 3 Min Freq Max Freq Hz 20.00 126
P1.1.21 Preset Speed 4 Min Freq Max Freq Hz 25.00 127
P1.1.22 Preset Speed 5 Min Freq Max Freq Hz 30.00 128
P1.1.23 Preset Speed 6 Min Freq Max Freq Hz 40.00 129
P1.1.24 Preset Speed 7 Min Freq Max Freq Hz 60.00 130
Code Parameter Min. Max. Unit Default ID Note
P1.2.1.1
Start/Stop logic selection 0 7 0 300 0 = Forw-Rev
1 = Start-Rev
2 = Start-Enable
3 = StartP-StopP
4 = Strt-MotP UP
5 = ForwR-RevR
6 = StartR-Rev
7 = StrtR-Enable
P1.2.1.2
MotPot ramp time 0.1 2000.0 Hz/s 10.0 331
P1.2.1.3
MotPotMemFreqRef 0 2 1 367 0 = No reset
1 = Res: stop+P.D.
2 = Res: P.D.
P1.2.1.4
Adjust input 0 5 0 493 0 = Not used
1 = AI1
2 = AI2
3 = AI3
4 = AI4
5 = Fieldbus
P1.2.1.5 Adjust minimum 0.0 100.0 % 0.0 494
P1.2.1.6 Adjust maximum 0.0 100.0 % 0.0 495