Firmware Manual

9000X AF Drives
6-8 For more information visit: www.eaton.com
MN04004001E
August 2010
Multi-Purpose Control Application
Basic Parameters (Control Keypad: Menu M1
G1.1)
Table 6-6: Basic Parameters — G1.1
Code Parameter Min. Max. Unit Default ID Note
P1.1.1 Min frequency 0.00 Par. 1.1.2 Hz 0.00 101
P1.1.2 Max frequency Par. 1.1.1 320.00 Hz 60.00 102 NOTE: If f
max
> than the motor
synchronous speed, check
suitability for motor and drive
system.
P1.1.3 Acceleration time 1 0.1 3000.0 s 3.0 103
P1.1.4 Deceleration time 1 0.1 3000.0 s 3.0 104
P1.1.5 Current limit 0.1 x I
H
2 x I
H
AI
L
107 I
H
is the nominal current rating of
the 9000X inverter.
P1.1.6
Nominal voltage of
the motor
180 690 V SVX-2: 230V
SVX-4: 460V
SVX-5: 575V
110 Motor nameplate value.
P1.1.7
Nominal frequency
of the motor
0.00 320.00 Hz 60.00 111 Motor nameplate value.
P1.1.8
Nominal speed of
the motor
0 65000 rpm 1720 112 Motor nameplate value.
P1.1.9
Nominal current of
the motor
0.1 x I
H
2 x I
H
AI
H
113 Check the rating plate of the motor.
P1.1.10 Power Factor 0.30 1.00 0.85 120 Check the rating plate of
the motor.
P1.1.11 Local control place 1 3 2 171 1 = I/O Terminal
2 = Keypad
3 = Fieldbus
P1.1.12 Remote control
place
1 3 1 172 1 = I/O Terminal
2 = Keypad
3 = Fieldbus
P1.1.13 Local reference 0 15 8 173 0 = AI1
1 = AI2
2 = AI1+AI2
3 = AI1-AI2
4 = AI2-AI1
5 = AI1xAI2
6 = AI1 Joystick
7 = AI2 Joystick
8 = Keypad
9 = Fieldbus
10 = Motor potentiometer
11 = AI1, AI2 minimum
12 = AI1, AI2 maximum
13 = Max frequency
14 = AI1/AI2 selection
15 = Encoder A1