Firmware Manual
9000X AF Drives
MN04004001E
For more information visit: www.eaton.com
6-1
August 2010
Chapter 6 — Multi-Purpose Control Application
Introduction
Select the Multi-Purpose Control Application in menu M5. See Chapter 5 of the 9000X AF
Drives User Manual.
Multi-purpose control application provides a wide range of parameters for controlling
motors. It can be used for various kinds of different processes, where wide flexibility of I/O
signals is needed and PID-control is not necessary (if you need PID-control functions, use
PID-control Application or Pump and Fan Control Application).
The frequency reference can be selected e.g. from the analog inputs, joystick control, motor
potentiometer and from a mathematical function of the analog inputs. There are parameters
also for Fieldbus communication. Multi-step speeds and jogging speed can also be selected if
digital inputs are programmed for these functions.
● The digital inputs and all the outputs are freely programmable and the application
supports all I/O-boards
Additional functions:
● Analog input signal range selection
● Two frequency limit supervisions
● Torque limit supervision
● Reference limit supervision
● Second ramps and S-shape ramp programming
● Programmable Start/Stop and Reverse logic
● DC-brake at start and stop
● Three skip frequency areas
● Programmable V/Hz curve and switching frequency
● Autorestart
● Motor thermal and stall protection: fully programmable; off, warning, fault
● Motor underload protection
● Input and output phase supervision
● Joystick hysteresis
● Possibility to connect the FB Process data to any parameter and some monitoring values
The parameters of the Multi-Purpose Control Application are explained in Chapter 8 of this
manual. The explanations are arranged according to the individual ID number of the parameter.