PID Control Application
Protections — G1.7 (Continued)
Autorestart Parameters (Control Keypad: Menu M1
G1.8)
Table 5-10: Autorestart Parameters — G1.8
Code Parameter Min. Max. Unit Default Cust ID Note
P1.7.21 Response to
thermistor fault
0 3 2 732 0 = No response
1 = Warning
2 = Fault.stop acc. to 1.4.7
3 = Fault.stop by coasting
P1.7.22 Response to
fieldbus fault
0 3 2 733 See P1.7.21
P1.7.23 Response to slot
fault
0 3 2 734 See P1.7.21
P1.7.24 No. of PT100 inputs 0 3 0 739
P1.7.25 Response to PT100
fault
0 3 2 740 0 = No response
1 = Warning
2 = Fault.stop acc. to 1.4.7
3 = Fault.stop by coasting
P1.7.26 PT100 warning limit -30.0 200.0 120.0 741
P1.7.27 PT100 fault limit -30.0 200.0 130.0 742
Code Parameter Min. Max. Unit Default Cust ID Note
P1.8.1 Wait time 0.10 10.00 s 0.50 717
P1.8.2 Trial time 0.00 60.00 s 30.00 718
P1.8.3 Start function 0 2 0 719 0 = Ramp
1 = Flying start
2 = According to par. 1.4.6
P1.8.4 Number of tries
after undervoltage
trip
0 10 0 720
P1.8.5 Number of tries
after overvoltage
trip
0 10 0 721
P1.8.6 Number of tries
after overcurrent
trip
0 3 0 722
P1.8.7 Number of tries
after reference trip
0 10 0 723
P1.8.8 Number of tries
after motor temp
fault trip
0 10 0 726
P1.8.9 Number of tries
after external fault
trip
0 10 0 725
P1.8.10 Number of tries
after underload
fault trip
0 10 0 738