Firmware Manual

9000X AF Drives
MN04004001E
For more information visit: www.eaton.com
5-7
August 2010
PID Control Application
Table 5-4: Input Signals — G1.2 (Continued)
Remember to place jumpers of block X2 accordingly. See 9000X AF Drives User Manual, Chapter 4.
Code Parameter Min. Max. Unit Default Cust ID Note
P1.2.7
Actual value 2 input 0 9 0 335 0 = Not used
1 = AI1 signal (c-board)
2 = AI2 signal (c-board)
3 = AI3
4 = AI4
5 = Fieldbus
(ProcessDataIN3)
6 = Motor torque
7 = Motor speed
8 = Motor current
9 = Motor power
P1.2.8 Actual value 1
minimum scale
-1000.0 1000.0 % 0.0 336 0 = No minimum scaling
P1.2.9 Actual value 1
maximum scale
-1000.0 1000.0 % 100.0 337 100 = No maximum scaling
P1.2.10 Actual value 2
minimum scale
-1000.0 1000.0 % 0.0 338 0 = No minimum scaling
P1.2.11 Actual value 2
maximum scale
-1000.0 1000.0 % 100.0 339 100 = No maximum scaling
P1.2.12
AI1 signal selection 0 A.1 377 TTF programming method used.
See Page 6-3.
P1.2.13 AI1 signal range 0 2 0 320 0 = Signal range 0 – 100%
1 = Signal range 20 – 100%
2 = Custom range
P1.2.14 AI1 custom
minimum setting
0.00 100.00 % 0.00 321
P1.2.15 AI1 custom
maximum setting
0.00 100.00 % 100.00 322
P1.2.16 AI1 inversion 0 1 0 323 0 = Not inverted
1 = Inverted
P1.2.17 AI1 filter time 0.00 10.00 s 0.10 324 0 = No filtering
P1.2.18
AI2 signal selection 0 A.2 388 TTF programming method used.
See Page 6-3.
P1.2.19 AI2 signal range 0 2 1 325 0 = 0 – 20 mA
1 = 4 – 20 mA
2 = Customized
P1.2.20 AI2 custom
minimum setting
0.00 100.00 % 0.00 326
P1.2.21 AI2 custom
maximum setting
0.00 100.00 % 100.00 327
P1.2.22 AI2 inversion 0 1 0 328 0 = Not inverted
1 = Inverted
P1.2.23 AI2 filter time 0.00 10.00 s 0.10 329 0 = No filtering
P1.2.24 Motor
potentiometer ramp
time
0.1 2000.0 /s 10.0 331