Firmware Manual
9000X AF Drives
MN04004001E
For more information visit: www.eaton.com
4-13
August 2010
Multi-Step Speed Control Application
Autorestart Parameters (Control Keypad: Menu M1
➔
G1.8)
Table 4-10: Autorestart Parameters — G1.8
Keypad Control (Control Keypad: Menu M2)
The parameters for the selection of control place and direction on the keypad are listed
below. See the Keypad control menu in the 9000X AF Drives User Manual.
Table 4-11: Keypad Control Parameters — M2
System Menu (Control Keypad: Menu M5)
For parameters and functions related to the general use of the drive, such as application
and language selection, customized parameter sets or information about the hardware and
software, see Chapter 5 in the 9000X AF Drives User Manual.
Expander Boards (Control Keypad: Menu M6)
The M6 menu shows the expander and option boards attached to the control board and
board-related information. For more information, see Chapter 5 in the 9000X AF Drives
User Manual.
Code Parameter Min. Max. Unit Default Cust ID Note
P1.8.1 Wait time 0.10 10.00 s 0.50 717
P1.8.2 Trial time 0.00 60.00 s 30.00 718
P1.8.3 Start function 0 2 0 719 0 = Ramp
1 = Flying start
2 = According to par. 1.4.6
P1.8.4 Number of tries after
undervoltage trip
0 10 0 720
P1.8.5 Number of tries after
overvoltage trip
0 10 0 721
P1.8.6 Number of tries after
overcurrent trip
0 3 0 722
P1.8.7 Number of tries after
reference trip
0 10 0 723
P1.8.8 Number of tries after
motor temp fault trip
0 10 0 726
P1.8.9 Number of tries after
external fault trip
0 10 0 725
P1.8.10 Number of tries after
underload fault trip
0 10 1 738
Code Parameter Min. Max. Unit Default Cust ID Note
P2.1 Control place 0 3 0 1685 0 = Keypad L/R
1 = Local
2 = Remote
3 = I/O force
R2.1 Keypad reference Par. 1.1.1 Par. 1.1.2 Hz
P2.3 Direction (on keypad) 0 1 0 123 0 = Forward
1 = Reverse
P2.4 Stop button 0 1 1 114 0 = Limited function of Stop
button
1 = Stop button always enabled
P2.5 Operate menu hide 0 1 0 1688 0 = No
1 = Yes