Firmware Manual
9000X AF Drives
MN04004001E
For more information visit: www.eaton.com
4-5
August 2010
Multi-Step Speed Control Application
Table 4-3: Basic Parameters — G1.1 (Continued)
Input Signals (Control Keypad: Menu M1
➔
G1.2)
Table 4-4: Input Signals — G1.2
Remember to place jumpers of block X2 accordingly. See 9000X AF Drives User Manual, Chapter 4.
CP = control place; cc = closing contact; oc = opening contact.
Code Parameter Min. Max. Unit Default Cust ID Note
P1.1.24 Preset speed 7 0.00 Par. 1.1.2 Hz 22.50 130 Multi-step speed 7
P1.1.25 Preset speed 8 0.00 Par. 1.1.2 Hz 25.00 133 Multi-step speed 8
P1.1.26 Preset speed 9 0.00 Par. 1.1.2 Hz 27.50 134 Multi-step speed 9
P1.1.27 Preset speed 10 0.00 Par. 1.1.2 Hz 30.00 135 Multi-step speed 10
P1.1.28 Preset speed 11 0.00 Par. 1.1.2 Hz 32.50 136 Multi-step speed 11
P1.1.29 Preset speed 12 0.00 Par. 1.1.2 Hz 35.00 137 Multi-step speed 12
P1.1.30 Preset speed 13 0.00 Par. 1.1.2 Hz 40.00 138 Multi-step speed 13
P1.1.31 Preset speed 14 0.00 Par. 1.1.2 Hz 45.00 139 Multi-step speed 14
P1.1.32 Preset speed 15 0.00 Par. 1.1.2 Hz 60.00 140 Multi-step speed 15
Code Parameter Min. Max. Unit Default Cust ID Note
P1.2.1
Start/Stop logic 0 6 0 300 DIN1 DIN2
0
1
2
3
4
5
6
Start fwd
Start/Stop
Start/Stop
Start pulse
Fwd
Start
/Stop
Start
/Stop
Start rvs
Rvs/Fwd
Run enable
Stop pulse
Rvs
Rvs/Fwd
Run enable
P1.2.2
DIN3 function 0 12 1 301 0 = Not used
1 = Ext. fault. closing cont.
2 = Ext. fault. opening cont.
3 = Run enable
4 = Acc./Dec. time select.
5 = Force CP to Local
6 = Force CP to Remote
7 = Rvs (if par. 1.2.1 = 3)
8 = Jogging speed
9 = Fault reset
10 = Acc./Dec. operation prohibit
11 = DC Braking command
12 = Preset speed
P1.2.3
AI1 signal
selection
0 A.1 377 TTF programming method used.
See Page 6-3.
P1.2.4 AI1 signal range 0 2 0 320 0 = 0…100%
1 = 20…100%
2 = Custom setting range