Firmware Manual

9000X AF Drives
3-14 For more information visit: www.eaton.com
MN04004001E
August 2010
Local/Remote Control Application
Table 3-10: Autorestart Parameters — G1.8 (Continued)
Keypad Control (Control Keypad: Menu M2)
The parameters for the selection of control place and direction on the keypad are listed
below. See the Keypad control menu in the 9000X AF Drives User Manual.
Table 3-11: Keypad Control Parameters — M2
System Menu (Control Keypad: Menu M5)
For parameters and functions related to the general use of the drive, such as application
and language selection, customized parameter sets or information about the hardware and
software, see Chapter 5 in the 9000X AF Drives User Manual.
Expander Boards (Control Keypad: Menu M6)
The M6 menu shows the expander and option boards attached to the control board and
board-related information. For more information, see Chapter 5 in the 9000X AF Drives
User Manual.
Note: Parameter P2.1, Control place, defaults to 3- I/O Select to disable the Keypad L/R
button since Local/Remote selection with this application is normally controlled with
Digital Input 6 (DIN6). Select Keypad L/R in parameter P2.1 to enable the Keypad L/R
button.
Code Parameter Min. Max. Unit Default Cust ID Note
P1.8.8 Number of tries
after motor temp
fault trip
0 10 0 726
P1.8.9 Number of tries
after external
fault trip
0 10 0 725
P1.8.10 Number of tries
after underload
fault trip
0 10 0 738
Code Parameter Min. Max. Unit Default Cust ID Note
P2.1 Control place 0 3 3 1685 Used to select Local Remote
operation from DIN6 or
keypad.
0 = Keypad L/R
1 = Local
2 = Remote
3 = I/O Select
R2.1 Keypad
reference
Par. 1.1.1 Par. 1.1.2 Hz
P2.2 Direction (on
keypad)
0 1 0 123 0 = Forward
1 = Reverse
P2.3 Stop button 0 1 1 114 0 = Limited function of Stop
button
1 = Stop button always
enabled
P2.4 Operate menu
hide
01 0 0 = No
1 = Yes