Firmware Manual

9000X AF Drives
MN04004001E
For more information visit: www.eaton.com
3-13
August 2010
Local/Remote Control Application
Table 3-9: Protections — G1.7 (Continued)
Autorestart Parameters (Control Keypad: Menu M1
G1.8)
Table 3-10: Autorestart Parameters — G1.8
Code Parameter Min. Max. Unit Default Cust ID Note
P1.7.14 Stall current 0.1 I
nMotor
x 2 A I
L
710
P1.7.15 Stall time limit 1.00 120.00 s 15.00 711
P1.7.16 Stall frequency
limit
1.0 Par. 1.1.2 Hz 25.0 712
P1.7.17 Underload
protection
0 3 0 713 0 = No response
1 = Warning
2 = Fault.stop acc. to 1.4.7
3 = Fault.stop by coasting
P1.7.18 Field weakening
area load
10 150 % 50 714
P1.7.19 Zero frequency
load
5.0 150.0 % 10.0 715
P1.7.20 Underload
protection time
limit
2 600 s 20 716
P1.7.21 Response to
thermistor fault
0 3 2 732 0 = No response
1 = Warning
2 = Fault.stop acc. to 1.4.7
3 = Fault.stop by coasting
P1.7.22 Response to
fieldbus fault
0 3 2 733 See P1.7.21
P1.7.23 Response to slot
fault
0 3 2 734 See P1.7.21
P1.7.24 FB MCW Bit 15 0 2 0 771 0 = No action
1 = Fault low
2 = Fault high
Code Parameter Min. Max. Unit Default Cust ID Note
P1.8.1 Wait time 0.10 10.00 s 0.50 717
P1.8.2 Trial time 0.00 60.00 s 30.00 718
P1.8.3 Start function 0 2 0 719 0 = Ramp
1 = Flying start
2 = According to par. 1.4.6
P1.8.4 Number of
tries after
undervoltage trip
0 10 0 720
P1.8.5 Number of tries
after overvoltage
trip
0 10 0 721
P1.8.6 Number of tries
after overcurrent
trip
0 3 0 722
P1.8.7 Number of tries
after reference
trip
0 10 0 723