Firmware Manual

9000X AF Drives
3-12 For more information visit: www.eaton.com
MN04004001E
August 2010
Local/Remote Control Application
Protections (Control Keypad: Menu M1
G1.7)
Table 3-9: Protections — G1.7
Code Parameter Min. Max. Unit Default Cust ID Note
P1.7.1 Response to
reference fault
0 5 0 700 0 = No response
1 = Warning
2 = Warning+Previous Freq.
3 = Wrng+PresetFreq 1.7.2
4 = Fault.stop acc. to 1.4.7
5 = Fault.stop by coasting
P1.7.2 4mA reference
fault frequency
0.00 Par. 1.1.2 Hz 0.00 728
P1.7.3 Response to
external fault
0 3 2 701 0 = No response
1 = Warning
2 = Fault.stop acc. to 1.4.7
3 = Fault.stop by coasting
P1.7.4 Input phase
supervision
0 3 3 730
P1.7.5 Response to
undervoltage
fault
1 3 0 727
P1.7.6 Output phase
supervision
0 3 2 702
P1.7.7 Earth fault
protection
0 3 2 703
P1.7.8 Thermal
protection of the
motor
0 3 2 704
P1.7.9 Motor ambient
temperature
factor
-100.0 100.0 % 0.0 705
P1.7.10 Motor cooling
factor at zero
speed
0.0 150.0 % 40.0 706
P1.7.11 Motor thermal
time constant
1 200 min 45 707
P1.7.12 Motor duty cycle 0 100 % 100 708
P1.7.13 Stall protection 0 3 0 709 0 = No response
1 = Warning
2 = Fault.stop acc. to 1.4.7
3 = Fault.stop by coasting