Firmware Manual

9000X AF Drives
3-10 For more information visit: www.eaton.com
MN04004001E
August 2010
Local/Remote Control Application
Skip Frequency Parameters (Control Keypad: Menu M1
G1.5)
Table 3-7: Skip Frequency Parameters — G1.5
Motor Control Parameters (Control Keypad: Menu M1
G1.6)
Table 3-8: Motor Control Parameters — G1.6
Code Parameter Min. Max. Unit Default Cust ID Note
P1.5.1 Skip frequency
range 1 low limit
0.00 par. 1.5.2 Hz 0.00 509
P1.5.2 Skip frequency
range 1 high
limit
0.00 par. 1.1.2 Hz 0.0 510 0 = Skip frequency range 1
not used
P1.5.3 Skip frequency
range 2 low limit
0.00 par. 1.5.2 Hz 0.00 511
P1.5.4 Skip frequency
range 2 high
limit
0.00 par. 1.1.2 Hz 0.0 512 0 = Skip frequency range 2
not used
P1.5.5 Skip frequency
range 3 low limit
0.00 par. 1.5.2 Hz 0.00 513
P1.5.6 Skip frequency
range 3 high
limit
0.00 par. 1.1.2 Hz 0.0 514 0 = Skip frequency range 3
not used
P1.5.7 Skip frequency
acc./dec. ramp
0.1 10.0 1.0 518
Code Parameter Min. Max. Unit Default Cust ID Note
P1.6.1
Motor control
mode
0 1/6 0 600 0 = Frequency control
1 = Speed control
Additionally for SPX:
2 = Torque control
3 = Closed loop speed ctrl
4 = Closed loop torque ctrl
P1.6.2
V/Hz
optimization
0 1 0 109 0 = Not used
1 = Automatic torque boost
P1.6.3
V/Hz ratio
selection
0 3 0 108 0 = Linear
1 = Squared
2 = Programmable
3 = Linear with flux optim.
P1.6.4
Field weakening
point
8.00 320.00 Hz 60.00 602
P1.6.5
Voltage at field
weakening point
10.00 200.00 % 100.00 603 n% x U
nmot
P1.6.6
V/Hz curve
midpoint
frequency
0.00 Par. 1.6.4 Hz 60.00 604
P1.6.7
V/Hz curve
midpoint voltage
0.00 100.00 % 100.00 605 n% x U
nmot
Parameter max. value = par.
1.6.5