Table 3-6: Drive Control Parameters — G1.4
Code Parameter Min. Max. Unit Default Cust ID Note
P1.4.1 Ramp 1 shape 0.0 10.0 s 0.0 500 0 = Linear
>0 = S-curve ramp time
P1.4.2 Ramp 2 shape 0.0 10.0 s 0.0 501 0 = Linear
>0 = S-curve ramp time
P1.4.3 Acceleration
time 2
0.1 3000.0 s 10.0 502
P1.4.4 Deceleration
time 2
0.1 3000.0 s 10.0 503
P1.4.5
Brake chopper 0 4 0 504 0 = Disabled
1 = Used when running
2 = External brake chopper
3 = Used when stopped/
running
4 = Used when running
(no testing)
P1.4.6 Start function 0 1 0 505 0 = Ramp
1 = Flying start
P1.4.7 Stop function 0 3 1 506 0 = Coasting
1 = Ramp
2 = Ramp+Run enable coast
3 = Coast+Run enable ramp
P1.4.8 DC braking
current
0.0 x I
H
2 x I
H
A 0.7 x I
H
507
P1.4.9 DC braking time
at stop
0.00 600.00 s 0.00 508 0 = DC brake is off at stop
P1.4.10 Frequency to
start DC braking
during ramp
stop
0.10 10.00 Hz 1.50 515
P1.4.11 DC braking time
at start
0.00 600.00 s 0.00 516 0 = DC brake is off at start
P1.4.12 Flux brake 0 1 0 520 0 = Off
1 = On
P1.4.13 Flux braking
current
0.1 x I
H
2 x I
H
AI
H