Firmware Manual
9000X AF Drives
3-6 For more information visit: www.eaton.com
MN04004001E
August 2010
Local/Remote Control Application
Table 3-4: Input Signals — G1.2 (Continued)
Rising edge required to start.
Code Parameter Min. Max. Unit Default Cust ID Note
P1.2.10 AI2 signal inversion 0 1 0 328 Analog input 2 reference
inversion yes/no
P1.2.11 AI2 signal filter time 0.00 10.00 s 0.10 329 Analog input 2 reference filter
time, constant
DIN4 DIN5
P1.2.12
Place B Start/Stop
logic selection
0 6 0 363 0
1
2
3
4
5
6
Start fwd
Start/Stop
Start/Stop
Start pulse
Fwd
Start
/Stop
Start
/Stop
Start rvs
Rvs/Fwd
Run enable
Stop pulse
Rvs
Rvs/Fwd
Run enable
P1.2.13 Reference scaling
minimum value
0.00 par. 1.2.17 Hz 0.00 303 Selects the frequency that
corresponds to the min.
reference signal
P1.2.14 Reference scaling
maximum value
0.00 320.00 Hz 0.00 304 Selects the frequency that
corresponds to the max.
reference signal
0.00 = No scaling
>0 = scaled max. value
P1.2.15 Motor
potentiometer ramp
time
0.1 2000.0 Hz/s 10.0 331
P1.2.16 Motor
potentiometer
frequency reference
memory reset
0 2 1 367 0 = No reset
1 = Reset if stopped or powered
down
2 = Reset if powered down
P1.2.17 Start pulse memory 0 1 0 498 0 = Run state not copied
1 = Run state copied