Firmware Manual
9000X AF Drives
MN04004001E
For more information visit: www.eaton.com
3-5
August 2010
Local/Remote Control Application
Input Signals (Control Keypad: Menu M1
➔
G1.2)
Table 3-4: Input Signals — G1.2
Rising edge required to start.
CP = control place.
Remember to place jumpers of block X2 accordingly. See 9000X AF Drives User Manual, Chapter 4.
Code Parameter Min. Max. Unit Default Cust ID Note
P1.2.1
Start/Stop logic
selection
0 8 0 300 DIN1 DIN2
0
1
2
3
4
5
6
7
8
Start fwd
Start/Stop
Start/Stop
Start pulse
Start fwd
Fwd
Start
/Stop
Start
/Stop
Start fwd*
Start rvs
Reverse
Run enable
Stop pulse
Mot.pot.UP
Rvs
Rvs/Fwd
Run enable
Mot.pot.UP
P1.2.2
DIN3 function 0 13 1 301 0 = Not used
1 = Ext. fault. closing cont.
2 = Ext. fault. opening cont.
3 = Run enable
4 = Acc./Dec. time select.
5 = Rvs (if par. 1.2.1 = 3)
6 = Jogging speed
7 = Fault reset
8 = Acc./Dec. operation prohibit
9 = DC Braking command
10 = Motor potentiometer DOWN
P1.2.3 AI1 signal
selection
0 A.1 337 TTF programming method used.
See Page 6-3.
P1.2.4 AI1 signal
inversion
0 1 0 323 Analog input 1 reference
inversion yes/no
P1.2.5 AI1 signal filter
time
0.00 10.00 s 0.10 324 Analog input 1 reference filter
time, constant
P1.2.6 AI2 signal
selection
0 A.2 388 TTF programming method used.
See Page 6-3.
P1.2.7 AI2 signal range 0 2 1 325 0 = 0 – 20 mA
1 = 4 – 20 mA
2 = custom setting range
P1.2.8 AI2 custom setting
minimum
0.00 100.00 % 0.00 326 Analog input 2 scale minimum
P1.2.9 AI2 custom setting
maximum
0.00 100.00 % 100.00 327 Analog input 2 scale maximum