Firmware Manual
9000X AF Drives
3-4 For more information visit: www.eaton.com
MN04004001E
August 2010
Local/Remote Control Application
Basic Parameters (Control Keypad: Menu M1
➔
G1.1)
Table 3-3: Basic Parameters — G1.1
Code Parameter Min. Max. Unit Default Cust ID Note
P1.1.1 Min frequency 0.00 Par. 1.1.2 Hz 0.00 101
P1.1.2 Max frequency Par. 1.1.1 320.00 Hz 60.00 102 NOTE: If f
max
> than the
motor synchronous speed,
check suitability for motor
and drive system.
P1.1.3 Acceleration time 1 0.1 3000.0 s 3.0 103
P1.1.4 Deceleration time 1 0.1 3000.0 s 3.0 104
P1.1.5 Current limit 0.1 x I
H
2 x I
H
AI
L
107
P1.1.6
Nominal voltage of the
motor
180 690 V P: 230V
P: 460V
P: 575V
110
P1.1.7
Nominal frequency of
the motor
30.00 320.00 Hz 60.00 111 Check the rating plate of the
motor.
P1.1.8
Nominal speed of the
motor
300 20 000 rpm 1720 112 The default applies for a
4-pole motor and a nominal
size frequency converter.
P1.1.9
Nominal current of the
motor
0.1 x I
H
2 x I
H
AI
H
113 Check the rating plate of the
motor.
P1.1.10
Power Factor 0.30 1.00 0.85 120 Check the rating plate of the
motor.
P1.1.11 Local Control Place 1 4 2 171 1 = I/O Terminal
2 = Keypad
3 = Fieldbus
4 = I/O Terminal B
P1.1.12 Remote Control Place 1 4 1 172 1 = I/O Terminal
2 = Keypad
3 = Fieldbus
4 = I/O Terminal B
P1.1.13 Local reference 0 4 2 173 0 = AI1
1 = AI2
2 = Keypad
3 = Fieldbus
4 = Motor potentiometer
P1.1.14 Remote reference 0 3 0 174 0 = AI1
1 = AI2
2 = Keypad
3 = Fieldbus
P.1.1.15 Identification 0 2 0 631 0 = Not used
1 = V/Hz
2 = V/Hz with boost
P.1.1.16 V/Hz Opt 0 1 0 109 0 = Not used
1 = Automatic torque boost
P1.1.17 Jogging speed
reference
0.00 Par. 1.1.2 Hz 0.00 124