Firmware Manual
9000X AF Drives
MN04004001E
For more information visit: www.eaton.com
2-9
August 2010
Standard Application
Motor Control Parameters — G1.6
Protections (Control Keypad: Menu M1
➔
G1.7)
Table 2-9: Protections — G1.7
Code Parameter Min. Max. Unit Default Cust ID Note
Closed Loop parameter group 1.6.14 (SPX only) (Continued)
P1.6.14.9 0-speed time at start 0 32000 ms 100 615
P1.6.14.10 0-speed time at stop 0 32000 ms 100 616
P1.6.14.11 Start-up torque 0 3 0 621 0 = Not used
1 = Torque memory
2 = Torque reference
3 = Start-up torque fwd/rev
P1.6.14.12 Start-up torque FWD -300.0 300.0 s 0.0 633
P1.6.14.13 Start-up torque REV -300.0 300.0 s 0.0 634
P1.6.14.15 Encoder filter time 0 1000 ms 0 618
P1.6.14.17 Current control
P gain
0.00 100.00 % 40.00 617
Code Parameter Min. Max. Unit Default Cust ID Note
P1.7.1 Response to
reference fault
0 6 6 700 0 = No response
1 = Warning
2 = Warning+Previous Freq.
3 = Wrng+PresetFreq 1.7.2
4 = Fault.stop acc. to 1.4.7
5 = Fault.stop by coasting
6 = Fault, Restart
P1.7.2 Reference fault
frequency
0.00 Par. 1.1.2 Hz 0.00 728
P1.7.3 Response to external
fault
0 3 2 701 0 = No response
1 = Warning
2 = Fault.stop acc. to 1.4.7
3 = Fault.stop by coasting
P1.7.4 Input phase
supervision
0 3 3 730
P1.7.5 Response to
undervoltage fault
1 3 0 727
P1.7.6 Output phase
supervision
0 3 2 702
P1.7.7 Earth fault protection 0 3 2 703
P1.7.8 Thermal protection of
the motor
0 3 2 704
P1.7.9 Motor ambient
temperature factor
-100.0 100.0 % 0.0 705
P1.7.10 Motor cooling factor at
zero speed
0.0 150.0 % 40.0 706
P1.7.11 Motor thermal time
constant
1 200 min 45 707
P1.7.12 Motor duty cycle 0 100 % 100 708
P1.7.13 Stall protection 0 3 0 709 0 = No response
1 = Warning
2 = Fault.stop acc. to 1.4.7
3 = Fault.stop by coasting