Firmware Manual
9000X AF Drives
2-4 For more information visit: www.eaton.com
MN04004001E
August 2010
Standard Application
Table 2-2: Monitoring Values (Continued)
Basic Parameters (Control Keypad: Menu M1
➔
G1.1)
Table 2-3: Basic Parameters — G1.1
Code Parameter Unit ID Description
V1.16 Analog I
out
mA 26 AO1
M1.17 Monitoring items Displays three selectable monitoring
values
Code Parameter Min. Max. Unit Default Cust ID Note
P1.1.1 Min frequency 0.00 Par. 1.1.2 Hz 0.00 101
P1.1.2 Max frequency Par.
1.1.1
320.00 Hz 60.00 102 NOTE: If f
max
> than the motor
synchronous speed, check
suitability for motor and drive
system.
P1.1.3 Acceleration time 1 0.1 3000.0 s 3.0 103
P1.1.4 Deceleration time 1 0.1 3000.0 s 3.0 104
P1.1.5 Current limit 0.1 x I
H
2 x I
H
AI
L
107
P1.1.6
Nominal voltage of the
motor
180 690 V P: 230V
P: 460V
P: 575V
110
P1.1.7
Nominal frequency of
the motor
30.00 320.00 Hz 60.00 111 Check the rating plate of the
motor.
P1.1.8
Nominal speed of the
motor
300 20 000 rpm 1720 112 The default applies for a 4-pole
motor and a nominal size
frequency converter.
P1.1.9
Nominal current of the
motor
0.1 x I
H
2 x I
H
AI
H
113 Check the rating plate of the
motor.
P1.1.10
Power Factor 0.30 1.00 0.85 120 Check the rating plate of the
motor.
P1.1.11 Local Control
Place
1 3 2 171 1 = I/O Terminal
2 = Keypad
3 = Fieldbus
P1.1.12 Remote Control
Place
1 3 1 172 1 = I/O Terminal
2 = Keypad
3 = Fieldbus
P1.1.13
Local reference 0 3 2 173 0 = AI1
1 = AI2
2 = Keypad
3 = Fieldbus
P1.1.14
Remote reference 0 3 0 174 0 = AI1
1 = AI2
2 = Keypad
3 = Fieldbus
P1.1.15 Identification 0 2 0 631 0 = Not used
1 = V/Hz
2 = V/Hz with boost
P1.1.16 V/Hz Opt 0 1 0 109 0 = Not used
1 = Automatic torque boost
P1.1.17 Preset speed 1 0.00 Par. 1.1.2 Hz 10.00 105 Speeds preset by operator.
P1.1.18 Preset speed 2 0.00 Par. 1.1.2 Hz 40.00 106