Firmware Manual
9000X AF Drives
8-86 For more information visit: www.eaton.com
MN04004001E
August 2010
Description of Parameters
Keypad Control Parameters
Unlike the parameters listed above, these parameters are located in the M2 menu of the
control keypad. The reference parameters do not have an ID number.
114 STOP button activated (P2.4, P2.6)
To make the STOP button a “hotspot” which always stops the drive regardless of the
selected control place, set the value of this parameter to 1.
See also ID125.
123 Keypad direction (P2.3)
0 Forward: The rotation of the motor is forward, when the keypad is the
active control place.
1 Reverse: The rotation of the motor is reversed, when the keypad is the
active control place.
For more information, see the 9000X AF Drives User Manual, Chapter 5, Keypad
Control Menu (M2).
R3.2 Keypad reference (R2.2)
The frequency reference can be adjusted from the keypad with this parameter.
The output frequency can be copied as the keypad reference by pushing the STOP
button for 3 seconds when you are on any of the pages of menu M2. For more
information, see the 9000X AF Drives User Manual, Chapter 5, Keypad Control Menu
(M2).
R3.4 PID reference 1 57 (R2.4)
The PID controller keypad reference can be set between 0% and 100%. This reference
value is the active PID reference if ID332 = 2.
R3.5 PID reference 2 57 (R2.5)
The PID controller keypad reference 2 can be set between 0% an 100%. This reference
is active if the DIN5 function = 13 and the DIN5 contact is closed.
R3.5 Torque reference 6 (R2.5)
Defines the torque reference from 0.0 to 100.0%.
1688 Operate Menu Hide — Disables operate menu to use monitor menu without auto