Description of Parameters
Figure 8-56: Frequency Converter Sleep Function
1017 Sleep delay 57 (P1.1.16)
The minimum amount of time the frequency has to remain below the Sleep level
before the frequency converter is stopped. See Figure 8-56.
1018 Wake-up level 57 (P1.1.17)
The wake-up level defines the level below which the actual value must fall or which
has to be exceeded before the Run state of the frequency converter is restored. See
Figure 8-56.
1019 Wake-up function 57 (P1.1.18)
This parameter defines whether the restoration of the Run state occurs when the
actual value signal falls below or exceeds the Wake-up level (ID1018). See Figure 8-56
and Table 8-14.
Application 5 has selections 01 and Application 7 selections 03 available.
Wake-Up Level
(ID1018)
Sleep Level
ID1016
t ID1017
Start/Stop Status of
the Var. Speed Drive
Stop
Running
Output
Frequency
Time
Actual
Value
Time
t ID1017