Firmware Manual
9000X AF Drives
MN04004001E
For more information visit: www.eaton.com
8-75
August 2010
Description of Parameters
Figure 8-54: Example of Parameter Setting
Variable Speed Drive and One Auxiliary Drive
1010 Start delay of auxiliary
drives
7 (P1.9.10)
The frequency of the drive controlled by the frequency converter must remain above
the start frequency of the auxiliary drive for the time defined with this parameter
before the auxiliary drive is started. The delay defined applies to all auxiliary drives.
This prevents unnecessary starts caused by the start limit being momentarily
exceeded. See Figure 8-54.
1011 Stop delay of auxiliary
drives
7 (P1.9.11)
The frequency of the drive controlled by the frequency converter must remain below
the stop limit of the auxiliary drive for the time defined with this parameter before the
auxiliary drive is stopped. The delay defined applies to all auxiliary drives. This
prevents unnecessary stops caused by the stop limit frequency momentarily dropping
below the limit. See Figure 8-54.
Output
Frequency
Start Freq. of Aux. Drive 1
(Par. ID1002 + 1 Hz)
Start Delay of the Aux
Drives (Par. ID1010)
Start Freq. of Aux. Drive 1
(Par. ID1003 - 1 Hz)
Frequency
After Starting
the Aux. Drive 1 Is
Par. ID1003 - 1 Hz
Frequency After
Starting the
Aux. Drive 1 is
Par. ID1003 + 1 Hz
Fmin Par.
ID101
Fmin
Par. ID101
Flow
Output
Frequency
Start Freq. of Aux Drive 1
(Par. ID1002 + 1 Hz)
Frequency
Decreases During
the Stop Delay
Frequency
Increases
During the
Start Delay
Stop Freq. of
Aux. Drive 1
(Par. ID1003 - 1 Hz)
Stop Delay of the Aux.
Drives (Par. ID1011)
Flow