Firmware Manual

9000X AF Drives
8-72 For more information visit: www.eaton.com
MN04004001E
August 2010
Description of Parameters
743 PT100 Numbers 2 6 (P1.7.28)
See (P1.7.24)
744 PT100 Flt Resp 2 6 (P1.7.29)
See (P1.7.25)
745 PT100 Warn Limit 2 6 (P1.7.30)
See (P1.7.26)
746 PT100 Fault Limit 2 6 (P1.7.31)
See (P1.7.27)
755 SafeDisable Mode 6 (P1.7.34)
With parameter, you set the mode of the Safe Disable.
770 Ref Fault Select 6 (P1.7.33)
With this parameter, you select the reference source to monitor for a Reference Fault.
771 FB MCW Bit 15 2, 3, 4, 5, 6, 7
Bit 15 of the Fieldbus Main Control Word is used to indicate the status of the signal
from the master controller. For example, the PROFIBUS board will set Bit 15 high if the
drive is addressed correctly and communicating with the master. Bit 15 is set low and
the red LED on the board is turned on if: 1.) The cable is broken or incorrectly
connected, 2.) The wrong configuration is set in the master, or 3.) The master is offline
or shut down. Set Fault Low for this enhanced monitoring of the PROFIBUS.
This bit can affect both the Communication Fault and Reference Fault. Other Fieldbus
boards or master controllers may indicate a problem by setting Bit 15 high. In this
case, select Fault High to respond to a Bit 15.
850 Fieldbus reference minimum
scaling
6 (P1.9.1)
851 Fieldbus reference maximum
scaling
6 (P1.9.2)
Use these two parameters to scale the fieldbus reference signal. Setting value limits:
0 ID850 ID851 ID102. If ID851 = 0, custom scaling is not used and the minimum
and maximum frequencies are used for scaling. The scaling functions as illustrated in
Figure 8-10. See Page A-5.
Note: Using this custom scaling function also affects the scaling of the actual value.