Firmware Manual

9000X AF Drives
MN04004001E
For more information visit: www.eaton.com
8-71
August 2010
Description of Parameters
732 Response to thermistor fault 234567 (P1.7.21)
0 No response
1 Warning
2 Fault, stop mode after fault according to ID506
3 Fault, stop mode after fault always by coasting
Setting the parameter to 0 will deactivate the protection.
733 Response to fieldbus fault 234567 (P1.7.22)
This sets the response mode for the fieldbus fault when a fieldbus board is used. For
more information, see the respective Fieldbus Board Manual.
See ID732.
734 Response to slot fault 234567 (P1.7.23)
This sets the response mode for a board slot fault caused by a missing or failed board.
See ID732.
738 Automatic restart: Number of
tries after underload fault trip
234567 (P1.8.10)
This parameter determines how many automatic restarts can be made during the trial
time set by ID718.
0 No automatic restart after an Underload fault trip
>0 Number of automatic restarts after an Underload fault trip
739 Number of PT100 inputs in use 567 (P1.7.24)
If a PT100 input board is installed in the frequency converter, this sets the number of
PT100 inputs in use. See the 9000X Option Board User Manual.
Note: If the selected value is greater than the actual number of PT100 inputs
being used, the display will read 200ºC. If the input is short-circuited the displayed
value is -30ºC.
740 Response to PT100 fault 567 (P1.7.25)
0 No response
1 Warning
2 Fault, stop mode after fault according to ID506
3 Fault, stop mode after fault always by coasting
741 PT100 warning limit 567 (P1.7.26)
Set here the limit at which the PT100 warning will be activated.
742 PT100 fault limit 567 (P1.7.27)
Set here the limit at which the PT100 fault (F56) will be activated.