Description of Parameters
Figure 8-49: Stall Characteristics Settings
Figure 8-50: Stall Time Count
710 Stall current limit 234567 (P1.7.14)
The current can be set to 0.1 – I
nMotor
*2. For a stall stage to occur, the current must
have exceeded this limit. See Figure 8-49. The software does not allow entering a
greater value than I
nMotor
*2. If ID113, nominal motor current is changed, this
parameter is automatically restored to the default value (I
L
). See Page A-4.
711 Stall time 234567 (P1.7.15)
This time can be set between 1.0 and 120.0s.
This is the maximum time allowed for a stall stage. The stall time is counted by an
internal up/down counter. If the stall time counter value goes above this limit the
protection will cause a trip (see ID709). See Page A-4.
Stall Area
ID710
ID712
f
I
Stall Time Counter
Trip Area
ID711
Stall
No Stall
Time
Trip/Warning
ID709