Firmware Manual
9000X AF Drives
8-54 For more information visit: www.eaton.com
MN04004001E
August 2010
Description of Parameters
Figure 8-44: DC-Braking Time when Stop Mode = Ramp
Par. ID506 = 1; Stop function = Ramp:
After the Stop command, the speed of the motor is reduced according to the set
deceleration parameters, as fast as possible, to the speed defined with ID515, where
the DC-braking starts.
The braking time is defined with ID508. If high inertia exists, it is recommended to use
an external braking resistor for faster deceleration. See Figure 8-44.
t
Output Frequency
Motor Speed
DC-Braking
RUN
STOP
ID515
t = ID508
f
out