Firmware Manual

9000X AF Drives
8-48 For more information visit: www.eaton.com
MN04004001E
August 2010
Description of Parameters
461
Autochange 4/Auxiliary drive 4
control
7 (P1.3.1.30)
Control signal for autochange/auxiliary drive 4. If three (or more) auxiliary drives are
used, we recommend the use of relay outputs, to connect drives 3 and 4. Since the
OPTA2 board only has two relay outputs it is advisable to purchase an I/O expander
board with extra relay outputs (e.g. OPTB5).
462
Autochange 5 control 7 (P1.3.1.31)
Control signal for autochange drive 5.
463
Analog input supervision limit 67 (P1.3.3.22, P1.3.1.22)
The selected analog input signal is beyond the set supervision limits (see ID372, ID373
and ID374).
464
Analog output 1 signal
selection
234567 (P1.3.1, P1.3.5.1, P1.3.3.1)
Connect the AO1 signal to the analog output of your choice with this parameter. For
more information about the TTF programming method, see Page 6-3.
471
Analog output 2 signal
selection
234567 (P1.3.12, P1.3.22, P1.3.6.1, P1.3.4.1)
Connect the AO2 signal to the analog output of your choice with this parameter. For
more information about the TTF programming method, see Page 6-3.
472 Analog output 2 function 234567 (P1.3.13, P1.3.23, P1.3.6.2, P1.3.4.2)
473 Analog output 2 filter time 234567 (P1.3.14, P1.3.24, P1.3.6.3, P1.3.4.3)
474 Analog output 2 inversion 234567 (P1.3.15, P1.3.25, P1.3.6.4, P1.3.4.4)
475 Analog output 2 minimum 234567 (P1.3.16, P1.3.26, P1.3.6.5, P1.3.4.5)
476 Analog output 2 scaling 234567 (P1.3.17, P1.3.27, P1.3.6.6, P1.3.4.6)
For more information on these five parameters, see the corresponding parameters for
the analog output 1, ID307 to ID311.
477 Analog output 2 offset 67 (P1.3.6.7, P1.3.4.7)
Add -100.0 to 100.0% to the analog output.
478
Analog output 3, signal
selection
67 (P1.3.7.1, P1.3.5.1)
See ID464.
479 Analog output 3, function 67 (P1.3.7.2, P1.3.5.2)
See ID307.
480 Analog output 3, filter time 67 (P1.3.7.3, P1.3.5.3)
See ID308.