Firmware Manual

9000X AF Drives
MN04004001E
For more information visit: www.eaton.com
8-45
August 2010
Description of Parameters
426
Autochange 1 interlock 7 (P1.2.6.18)
Contact closed: Interlock of autochange drive 1 or auxiliary drive 1 activated.
Default programming: A.2.
427
Autochange 2 interlock 7 (P1.2.6.19)
Contact closed: Interlock of autochange drive 2 or auxiliary drive 2 activated.
Default programming: A.3.
428
Autochange 3 interlock 7 (P1.2.6.20)
Contact closed: Interlock of autochange drive 3 or auxiliary drive 3 activated.
429
Autochange 4 interlock 7 (P1.2.6.21)
Contact closed: Interlock of autochange drive 4 or auxiliary drive 4 activated.
430
Autochange 5 interlock 7 (P1.2.6.22)
Contact closed: Interlock of autochange drive 5 activated.
431
PID reference 2 7 (P1.2.6.23)
Contact open: PID controller reference selected with ID332.
Contact closed: PID controller keypad reference 2 selected with ID371.
432
Ready 67 (P1.3.3.1, P1.3.1.1)
The frequency converter is ready to operate.
433
Run 67 (P1.3.3.2, P1.3.1.2)
The frequency converter is operating (the motor is running).
434
Fault 67 (P1.3.3.3, P1.3.1.3)
A fault trip has occurred.
Default programming: A.1 for Application 7 and B.2 for Application 6.
435
Inverted fault 67 (P1.3.3.4, P1.3.1.4)
No fault trip has occurred.
436
Warning 67 (P1.3.3.5, P1.3.1.5)
General warning signal.