Firmware Manual

9000X AF Drives
MN04004001E
For more information visit: www.eaton.com
8-43
August 2010
Description of Parameters
403
Start signal 1 6 (P1.2.7.1)
Signal selection 1 for the start/stop logic.
Default programming A.1.
404
Start signal 2 6 (P1.2.7.2)
Signal selection 2 for the start/stop logic.
Default programming A.2.
405
External fault (close) 67 (P1.2.7.11, P1.2.6.4)
Contact closed: Fault is displayed and motor stopped
406
External fault (open) 67 (P1.2.7.12, P1.2.6.5)
Contact open: Fault is displayed and motor stopped
407
Run enable 67 (P1.2.7.3, P1.2.6.6)
Contact open: Start of motor disabled
Contact closed: Start of motor enabled
408
Acceleration/Deceleration time
selection
67 (P1.2.7.13, P1.2.6.7)
Contact open: Acceleration/Deceleration time 1 selected
Contact closed: Acceleration/Deceleration time 2 selected
Set Acceleration/Deceleration times with ID103 and ID104.
409
Control from I/O terminal 67 (P1.2.7.18, P1.2.6.8)
Contact closed: Force control place to I/O terminal
410
Control from keypad 67 (P1.2.7.19, P1.2.6.9)
Contact closed: Force control place to keypad
412
Reverse 67 (P1.2.7.4, P1.2.6.11)
Contact open: Direction forward
Contact closed: Direction reverse
413
Jogging speed 67 (P1.2.7.10, P1.2.6.13)
Contact closed: Jog speed selected for frequency reference
See parameter ID124.
Default programming: A.4.