Firmware Manual
9000X AF Drives
8-42 For more information visit: www.eaton.com
MN04004001E
August 2010
Description of Parameters
Figure 8-38: Reducing Acceleration and Deceleration Times
Figure 8-39: Reducing Torque Supervision Limit
401 Reducing of acceleration and
deceleration times
6 (P1.2.6.3)
See ID399.
Acceleration and deceleration times can be reduced with the free analog input signal
according to the following formulas:
Reduced time = set acc./deceler. time (ID103, ID104; ID502, ID503) divided by the factor
R from Figure 8-38.
402 Reducing of torque supervision limit 6 (P1.2.6.4)
See ID399.
The set torque supervision limit can be reduced with the free analog input signal
between 0 and the set supervision limit, ID349. See Figure 8-39.
Free
Analog
Input
Signal Range
2
Factor R
1
10
Free
Analog
Input
Signal Range
100%
ID349
Torque
Limit
0