Description of Parameters
367 Motor potentiometer memory
reset (Frequency reference)
3567 (P1.2.23, P1.2.28, P1.2.1.3, P1.2.1.16)
0 No reset
1 Memory reset in stop and power down
2 Memory reset in power down
370 Motor potentiometer memory
reset (PID reference)
57 (P1.2.29, P1.2.1.17)
0 No reset
1 Memory reset in stop and power down
2 Memory reset in power down
371 PID reference 2 (Place A
additional reference)
7 (P1.2.1.4)
If the PID reference 2 enable input function ID330 = TRUE, this parameter deļ¬nes
which reference place is selected as PID controller reference.
0 AI1 reference (terminals 2 and 3, e.g. potentiometer)
1 AI2 reference (terminals 5 and 6, e.g. transducer)
2 AI3 reference
3 AI4 reference
4 PID reference 1 from keypad
5 Reference from Fieldbus (FBProcessDataIN3)
6 Motor potentiometer
7 PID reference 2 from keypad
If value 6 is selected for this parameter, the functions Motor potentiometer DOWN and
Motor potentiometer UP must be connected to digital inputs (ID417 and ID418).
372 Supervised analog input 7 (P1.3.2.13)
0 Analog reference from AI1 (terminals 2 and 3, e.g. potentiometer)
1 Analog reference from AI2 (terminals 4 and 5, e.g. transducer)
373 Analog input limit supervision 7 (P1.3.2.14)
If the value of the selected analog input goes under/over the set limit (ID374), this
function generates a warning message through the digital output or the relay outputs
depending on to which output the supervision function (ID463) is connected.
0 No supervision
1 Low limit supervision
2 High limit supervision