Firmware Manual
9000X AF Drives
8-34 For more information visit: www.eaton.com
MN04004001E
August 2010
Description of Parameters
Figure 8-30: Place B Start Forward/Start Reverse
Figure 8-31: Place B Start, Stop, Reverse
363 Start/Stop logic selection,
place B
3 (P1.2.15)
0 DIN4: closed contact = start forward
DIN5: closed contact = start reverse
The first selected direction has the highest priority.
When the DIN4 contact opens the direction of rotation starts to change.
If Start forward (DIN4) and Start reverse (DIN5) signals are active
simultaneously, the Start forward signal (DIN4) has priority.
1 DIN4: closed contact = start — open contact = stop
DIN5: closed contact = reverse — open contact = forward
See Figure 8-31.
FWD
REV
DIN4
DIN5
t
Output
Frequency
Stop Function
(ID506) = Coasting
1 2 3
FWD
REV
DIN4
DIN5
Output
Frequency
Stop Function
(ID506) = Coasting
t