Firmware Manual
9000X AF Drives
1-4 For more information visit: www.eaton.com
MN04004001E
August 2010
Basic Application
Basic Parameters (Control Keypad: M1
➔
G1.1)
Table 1-3: Basic Parameters — G1
Code Parameter Min. Max. Unit Default Cust ID Note
P1.1 Min frequency 0.00 Par. 1.2 Hz 0.00 101
P1.2 Max frequency Par. 1.1 320.00 Hz 60.00 102 NOTE: If f
max
> than the motor
synchronous speed, check
suitability for motor and drive
system.
P1.3 Acceleration time 1 0.1 3000.0 s 3.0 103
P1.4 Deceleration time 1 0.1 3000.0 s 3.0 104
P1.5 Current limit 0.1 x I
H
2 x I
H
AI
L
107
P1.6
Nominal voltage of the
motor
180 690 V P: 230V
P: 460V
P: 575V
110 Check the rating plate of the
motor.
P1.7
Nominal frequency of
the motor
30.00 320.00 Hz 60.00 111 Check the rating plate of the
motor.
P1.8
Nominal speed of the
motor
300 20 000 rpm 1720 112 Check the rating plate of the
motor. The default applies for a
4-pole motor and a nominal size
frequency converter.
P1.9
Nominal current of the
motor
0.1 x I
H
2 x I
H
AI
H
113 Check the rating plate of the
motor.
P1.10 Preset speed 1 0.00 Par 1.1.2 Hz 10.00 105 Speeds preset by operator
P1.11 Preset speed 2 0.00 Par 1.1.2 Hz 40.00 106 Speeds preset by operator
P1.12 Input phase
supervision
0 3 730 0 = No action
1 = Working
2 = Fault
3 = Fault, coast