Firmware Manual

9000X AF Drives
MN04004001E
For more information visit: www.eaton.com
8-29
August 2010
Description of Parameters
348 Torque limit, supervision
function
34567 (P1.3.14, P1.3.4.5, P1.3.2.5)
0 No supervision
1 Low limit supervision
2 High limit supervision
3 Brake-off control (Application 6 only, see Page A-1.)
If the calculated torque value falls below or exceeds the set limit (ID349) this function
generates a warning message via the digital output DO1 or via a relay output RO1 or
RO2 depending on:
1) the settings of ID312 to ID314 (Applications 3, 4, 5) or …
2) to which output the supervision signal (ID451) is connected (Applications 6 and 7).
349 Torque limit, supervision value 34567 (P1.3.15, P1.3.4.6, P1.3.2.6)
Set here the torque value to be supervised by ID348.
Applications 3 and 4:
The torque supervision value can be reduced below the setpoint with the external free
analog input signal, see ID361 and ID362.
350 Reference limit, supervision
function
34567 (P1.3.16, P1.3.4.7, P1.3.2.7)
0 No supervision
1 Low limit supervision
2 High limit supervision
If the reference value falls below or exceeds the set limit (ID351), this function
generates a warning message via the digital output DO1 or via a relay output RO1 or
RO2 depending on:
1) the settings of ID312 to ID314 (Applications 3, 4, 5) or …
2) to which output the supervision signal (ID451) is connected (Applications 6 and 7).
The supervised reference is the current active reference. It can be place A or B
reference depending on DIN6 input, or panel reference if the panel is the active control
place.
351 Reference limit, supervision
value
34567 (P1.3.17, P1.3.4.8, P1.3.2.8)
The frequency value to be supervised by ID350.