August 2010
Description of Parameters
333 PID controller actual value
selection
57 (P1.2.8, P1.2.1.8)
This parameter selects the PID controller actual value.
0 Actual value 1
1 Actual value 1 + Actual value 2
2 Actual value 1 – Actual value 2
3 Actual value 1 * Actual value 2
4 Greater one of Actual value 1 and Actual value 2
5 Smaller one of Actual value 1 and Actual value 2
6 Mean value of Actual value 1 and Actual value 2
7 Square root of Actual value 1 + Square root of Actual value 2
334 Actual value 1 selection 57 (P1.2.9, P1.2.1.9)
335 Actual value 2 selection 57 (P1.2.10, P1.2.1.10)
0 Not used
1 AI1 (control board)
2 AI2 (control board)
3 AI3
4 AI4
5 Fieldbus (Actual value 1: FBProcessDataIN2; Actual value 2:
FBProcessDataIN3)
Application 5:
6 Motor torque
7 Motor speed
8 Motor current
9 Motor power
10 Encoder frequency (for Actual value 1 only)
336 Actual value 1 minimum scale 57 (P1.2.11, P1.2.1.11)
Sets the minimum scaling point for Actual value 1. See Figure 8-22.
337 Actual value 1 maximum scale 57 (P1.2.12, P1.2.1.12)
Sets the maximum scaling point for Actual value 1. See Figure 8-22.
338 Actual value 2 minimum scale 57 (P1.2.13, P1.2.1.13)
Sets the minimum scaling point for Actual value 2. See Figure 8-22.
339 Actual value 2 maximum scale 57 (P1.2.14, P1.2.1.14)
Sets the maximum scaling point for Actual value 2. See Figure 8-22.