Description of Parameters
319 DIN2 function 5 (P1.2.1)
This parameter has 14 selections. If digital input DIN2 is not used, set this value to 0.
0 Not used
1 External fault:
Contact closed = Fault is displayed and the motor stopped when the input
is active
2 External fault:
Contact open = Fault is displayed and the motor stopped when the input
is not active
3 Run enable:
Contact open = Start of motor disabled
Contact closed = Start of motor enabled
4 Acceleration or deceleration time selection:
Contact open = Acceleration/Deceleration time 1 selected
Contact closed = Acceleration/Deceleration time 2 selected
5 Closing contact: Force control place to I/O terminal
6 Closing contact: Force control place to keypad
7 Closing contact: Force control place to fieldbus
When the control place is forced to change, the values of Start/Stop,
Direction and the Reference valid in the respective control place, are used
(reference according to ID343, ID121 and ID122).
Note: The value of ID125 (Keypad Control Place) does not change. When
DIN2 opens the control place is selected according to keypad control
place selection.
8 Reverse:
Contact open = Forward
Contact closed = Reverse
Note: If several inputs are programmed to reverse, one active contact is
enough to set the direction to reverse.
9 Jog speed (see ID124)
Contact closed = Jogging speed selected for frequency reference
10 Fault reset
Contact closed = All faults reset
11 Acceleration/Deceleration prohibited:
Contact closed = No acceleration or deceleration possible until the
contact is opened
12 DC braking command:
Contact closed = In Stop mode, the DC braking operates until the contact
is opened. See Figure 8-17.
13 Motor potentiometer UP:
Contact closed = Reference increases until the contact is opened.