Firmware Manual

9000X AF Drives
MN04004001E
For more information visit: www.eaton.com
8-19
August 2010
Description of Parameters
Table 8-8: Output Signals Via DO1 and Output Relays RO1 and RO2
Setting value Signal content
0 = Not used Out of operation
Digital output DO1 sinks current and programmable relay (RO1, RO2) is activated when:
1 = Ready The frequency converter is ready to operate
2 = Run The frequency converter is operating (motor is running)
3 = Fault A fault trip has occurred
4 = Fault inverted A fault trip not
occurred
5 = Overheat warning The heat-sink temperature exceeds +70°C
6 = External fault or warning Fault or warning depending on ID701
7 = Reference fault or warning Fault or warning depending on ID700
• if analog reference is 4 – 20 mA and signal is <4 mA
8 = Warning Always if a warning exists
9 = Reversed The reverse command has been selected
10 = Preset speed 1 (Application 2)
10 = Jogging speed (Applications 3456)
The preset speed has been selected with digital input
The jogging speed has been selected with digital input
11 = At speed The output frequency has reached the set reference
12 = Motor regulator activated Overvoltage or overcurrent regulator was activated
13 = Output frequency limit supervision The output frequency is outside the set supervision low
limit/high limit (ID315 and ID316)
14 = Control from I/O terminals
(Application 2)
14 = Output frequency limit 2 supervision
(Applications 3456)
I/O control mode selected (in menu M2)
The output frequency goes outside the set supervision low
limit/high limit (ID346 and ID347)
15 = Thermistor fault or warning
(Application 2)
15 = Torque limit supervision
(Applications 3456)
The thermistor input of option board indicates
overtemperature. Fault or warning depending on ID732.
The motor torque is beyond the set supervision low limit/
high limit (ID348 and ID349).
16 = Fieldbus input data
(Application 2)
16 = Reference limit supervision
(Applications 3456)
Fieldbus input data (FBFixedControlWord) to DO/RO.
Active reference goes beyond the set supervision low limit/
high limit (ID350 and ID351)
17 = External brake control
(Applications 3456)
External brake ON/OFF control with programmable delay
(ID352 and ID353)
18 = Control from I/O terminals
(Applications 3456)
External control mode (Menu M2; ID125)
19 = Frequency converter temperature
limit supervision (Applications 3456)
Frequency converter heatsink temperature goes beyond the
set supervision limits (ID354 and ID355).
20 = Unrequested rotation direction
(Applications 345)
20 = Reference inverted (Application 6)
Rotation direction is different from the requested one.
21 = External brake control inverted
(Applications 3456)
External brake ON/OFF control (ID352 and ID353); Output
active when brake control is OFF