Firmware Manual
9000X AF Drives
8-18 For more information visit: www.eaton.com
MN04004001E
August 2010
Description of Parameters
Table 8-7: Analog Output Scaling
Figure 8-15: Analog Output Scaling
311 Analog output scale 234567 (P1.3.6, P1.3.5.6, P1.3.3.6)
Scaling factor for analog output.
Signal Max. value of the signal
Output frequency Max frequency (ID102)
Freq. Reference Max frequency (ID102)
Motor speed Motor nom. speed 1xn
mMotor
Output current Motor nom. current 1xI
nMotor
Motor torque Motor nom. torque 1xT
nMotor
Motor power Motor nom. power 1xP
nMotor
Motor voltage 100% x V
nMotor
DC-link voltage
PI-ref. value
PI act. value 1
PI act. value 2
PI error value
PI output
1000 V
100% x ref. value max.
100% x actual value max.
100% x actual value max.
100% x error value max.
100% x output max.
312 Digital output function 23456 (P1.3.7, P1.3.1.2)
313 Relay output 1 function 2345 (P1.3.8, P1.3.1.3)
314 Relay output 2 function 2345 (P1.3.9)
Analog
Output
Current
20 mA
12 mA
10 mA
ID310 = 1
4 mA
ID310 = 0
0 mA
0 0.5 1.0
ID311 =
50%
Max. Value
of Signal
Selected
by ID307
ID311 = 200%
ID311 =
100%