Firmware Manual

9000X AF Drives
8-12 For more information visit: www.eaton.com
MN04004001E
August 2010
Description of Parameters
Figure 8-8: Start Pulse/Stop Pulse
2 DIN1: closed contact = start — open contact = stop
DIN2: closed contact = start enabled — open contact = start disabled and
drive stopped if running, see Figure 8-8.
3 3-wire connection (pulse control):
DIN1: closed contact = start pulse
DIN2: open contact = stop pulse
(DIN3 can be programmed for reverse command), see Figure 8-8.
t
Output
Frequency
Stop Function
(ID506) = Coasting
If Start and Stop pulses are
simultaneous the Stop pulse
overrides the Start pulse
REV
DIN1
Start
DIN2
Stop