Firmware Manual

9000X AF Drives
8-10 For more information visit: www.eaton.com
MN04004001E
August 2010
Description of Parameters
Table 8-6: Selections for ID173, ID174 and ID175
Application
2 – 4 5 6 7Select
0 Analog voltage ref.
Terminals 2 – 3
Analog voltage ref.
Terminals 2 – 3
Analog voltage ref.
Terminals 2 – 3
Analog voltage ref.
Terminals 2 – 3
1 Analog current ref.
Terminals 4 – 5
Analog current ref.
Terminals 4 – 5
Analog current ref.
Terminals 4 – 5
Analog current ref.
Terminals 4 – 5
2 Keypad reference
(Menu M2)
AI3 AI1+AI2 AI3
3 Fieldbus reference
AI4 AI1 – AI2 AI4
4 Motor potentiometer
(App #3 only)
Keypad reference
(Menu M2)
AI2 – AI1 Keypad reference
(Menu M2)
5 Fieldbus
reference
AI1 x AI2 Fieldbus
reference
6 Potentiometer ref. AI1 joystick Potentiometer ref.
7 PID controller ref. AI2 joystick PID controller ref.
8 Keypad reference
(Menu M2)
9 Fieldbus reference
10 Potentiometer
reference;
controlled with
DIN5 (TRUE =
increase) and DIN6
(TRUE = decrease)
11 AI1 or AI2,
whichever is lower
12 AI1 or AI2,
whichever is greater
13 Max. frequency
(recommended in
torque control only)
14 AI1/AI2 selection
FB Speed Reference
176 Force local 6 (P1.2.7.19)
Forces control place to I/O terminal.
177 Force remote 6 (P1.2.7.20)
Forces control place to keypad.
300 Start/Stop logic selection 2346 (P1.2.1, P1.2.1.1)
0 DIN1: closed contact = start forward
DIN2: closed contact = start reverse