Firmware Manual

9000X AF Drives
7-26 For more information visit: www.eaton.com
MN04004001E
August 2010
Pump and Fan Control Application
Table 7-20: Pump and Fan Control Parameters — G1.9 (Continued)
Keypad Control (Control Keypad: Menu M2)
This menu provides the parameters for the setting of the keypad frequency reference, the
selection of motor direction when in keypad operation, and when the STOP button is active.
Table 7-21: Keypad Control Parameters — M2
Code Parameter Min. Max. Unit Default Cust ID Note
P1.9.22 Frequency increase
delay
0.0 300.0 s 0.0 1026 0.0 = No delay
300.0 = No frequency drop
P1.9.23 Interlock selection 0 2 0 1032 0 = Interlocks not used
1 = Set new interlock last;
update order after value of
P1.9.26 or Stop state
2 = Stop and update order
immediately
P1.9.24 Autochange 0 1 0 1027 0 = Not used
1 = Autochange used
P1.9.25 Autochange and
interlock
automatics
selection
0 1 0 1028 0 = Auxiliary drives only
1 = All drives
P1.9.26 Autochange
interval
0.0 3000.0 h 48.0 1029 0.0 = TEST = 40 s
P1.9.27 Autochange;
maximum number
of auxiliary drives
0 4 1 1030
P1.9.28 Autochange
frequency limit
0.00 P1.1.2 Hz 30.00 1031
P1.9.29 Actual value special
display minimum
0.0 3000.0 0.0 1033
P1.9.30 Actual value special
display maximum
0.0 3000.0 10.0 1034
P1.9.31 Actual value special
display decimals
0 4 1 1035
Code Parameter Min. Max. Unit Default Cust ID Note
P2.1 Control place 0 2 0 1685 0 = Keypad L/R
1 = Local
2 = Remote
3 = I/O select
R2.1 Keypad reference P1.1.1 P1.1.2 Hz
P2.2 Direction (on
keypad)
0 1 0 123 0 = Forward
1 = Reverse
P2.3 PID reference 1 0.00 100.00 % 0.00
P2.4 PID reference 2 0.00 100.00 % 0.00
P2.5 Stop button active 0 1 1 114 0 = Limited function of Stop
button
1 = Stop button always enabled
P2.6 Operate menu hide 0 1 0 0 = No
1 = Yes