Pump and Fan Control Application
Pump and Fan Control Parameters (Control Keypad: Menu M1
➔
G1.9)
Table 7-20: Pump and Fan Control Parameters — G1.9
Code Parameter Min. Max. Unit Default Cust ID Note
P1.9.1 Number of auxiliary
drives
0 4 0 1001
P1.9.2 Start frequency.
auxiliary drive 1
P1.9.3 320.00 Hz 61.00 1002
P1.9.3 Stop frequency.
auxiliary drive 1
P1.1.1 P1.9.2 Hz 10.00 1003
P1.9.4 Start frequency.
auxiliary drive 2
P1.9.5 320.00 Hz 61.00 1004
P1.9.5 Stop frequency.
auxiliary drive 2
P1.1.1 P1.9.4 Hz 10.00 1005
P1.9.6 Start frequency.
auxiliary drive 3
P1.9.7 320.00 Hz 61.00 1006
P1.9.7 Stop frequency.
auxiliary drive 3
P1.1.1 P1.9.6 Hz 10.00 1007
P1.9.8 Start frequency.
auxiliary drive 4
P1.9.9 320.00 Hz 61.00 1008
P1.9.9 Stop frequency.
auxiliary drive 4
P1.1.1 P1.9.8 Hz 10.00 1009
P1.9.10 Start delay.
auxiliary drives
0.0 300.0 s 4.0 1010
P1.9.11 Stop delay.
auxiliary drives
0.0 300.0 s 2.0 1011
P1.9.12 Reference step.
auxiliary drive 1
0.0 100.0 % 0.0 1012
P1.9.13 Reference step.
auxiliary drive 2
0.0 100.0 % 0.0 1013
P1.9.14 Reference step.
auxiliary drive 3
0.0 100.0 % 0.0 1014
P1.9.15 Reference step.
auxiliary drive 4
0.0 100.0 % 0.0 1015
P1.9.16 PID controller
bypass
0 1 0 1020 1 = PID contr. bypassed
P1.9.17 Analog input
selection for input
pressure
measurement
0 5 0 1021 0 = Not used
1 = AI1
2 = AI2
3 = AI3
4 = AI4
5 = Fieldbus signal
P1.9.18 Input pressure
high limit
0.0 100.0 % 30.00 1022
P1.9.19 Input pressure
low limit
0.0 100.0 % 20.00 1023
P1.9.20 Output pressure
drop
0.0 100.0 % 30.00 1024
P1.9.21 Frequency drop
delay
0.0 300.0 s 0.0 1025 0.0 = No delay
300.0 = No frequency drop