Firmware Manual

9000X AF Drives
7-24 For more information visit: www.eaton.com
MN04004001E
August 2010
Pump and Fan Control Application
Table 7-18: Protections — G1.7 (Continued)
Autorestart Parameters (Control Keypad: Menu M1
G1.8)
Table 7-19: Autorestart Parameters — G1.8
Code Parameter Min. Max. Unit Default Cust ID Note
P1.7.22 Response to
fieldbus fault
0 3 2 733 See P1.7.3
P1.7.23 Response to slot
fault
0 3 2 734 See P1.7.3
P1.7.24
No. of PT100 inputs 0
3 0 739
P1.7.25 Response to PT100
fault
0 1 1 740 0 = Fault stored to history
1 = Fault not stored to history
P1.7.26 PT100 warning limit -30.0 200.0 °C 120.0 741
P1.7.27 PT100 fault limit -30.0 200.0 °C 130.0 742
P1.7.28 FB MCW Bit 15 0 2 0 771 0 = No action
1 = Fault low
2 = Fault high
Code Parameter Min. Max. Unit Default Cust ID Note
P1.8.1 Wait time 0.10 10.00 s 0.50 717
P1.8.2 Trial time 0.00 60.00 s 30.00 718
P1.8.3 Start mode 0 2 0 719 0 = Ramp
1 = Flying start
2 = Start per P1.4.6
P1.8.4 Number of tries
after undervoltage
trip
0 10 1 720
P1.8.5 Number of tries
after overvoltage
trip
0 10 1 721
P1.8.6 Number of tries
after overcurrent
trip
0 3 1 722
P1.8.7 Number of tries
after 4mA
0 10 1 723
P1.8.8 Number of tries
after motor
temperature fault
trip
0 10 1 726
P1.8.9 Number of tries
after external fault
trip
0 10 0 725
P1.8.10 Number of tries
after underload
fault trip
0 10 1 738