Firmware Manual
9000X AF Drives
7-22 For more information visit: www.eaton.com
MN04004001E
August 2010
Pump and Fan Control Application
Skip Frequencies (Control Keypad: Menu M1
➔
G1.5)
Table 7-16: Skip Frequencies— G1.5
Motor Control Parameters (Control Keypad: Menu M1
➔
G1.6)
Table 7-17: Motor Control Parameters — G1.6
Code Parameter Min. Max. Unit Default Cust ID Note
P1.5.1 Skip frequency
range 1 low limit
0.0 P1.5.2 Hz 0.00 509
P1.5.2 Skip frequency
range 1 high limit
P1.5.1 320.00 Hz 0.00 510 0.00 = Skip frequency range 1
not used
P1.5.3 Skip frequency
range 2 low limit
0.00 P1.5.4 Hz 0.00 511
P1.5.4 Skip frequency
range 2 high limit
P1.5.3 320.00 Hz 0.00 512 0.00 = Skip frequency range 2
not used
P1.5.5 Skip frequency
range 3 low limit
0.00 P1.5.6 Hz 0.00 513
P1.5.6 Skip frequency
range 3 high limit
P1.5.5 320.00 Hz 0.00 514 0.00 = Skip frequency range 3
not used
P1.5.7 Prohibit acc./dec.
ramp
0.1 10.0 1.0 518 Multiplier for ramp time in
skip frequency range, e.g.
0.1 – 10% of normal ramp time
Code Parameter Min. Max. Unit Default Cust ID Note
P1.6.1
Motor control mode 0 1 0 600 0 = Frequency control
1 = Speed control
P1.6.2
V/Hz optimization 0 1 0 109 0 = Not used
1 = Automatic torque boost
P1.6.3
V/Hz ratio selection 0 3 0 108 0 = Linear
1 = Squared
2 = Programmable
3 = Linear with flux optim.
P1.6.4
Field weakening
point
8.00 320.00 Hz 60.00 602
P1.6.5
Voltage at field
weakening point
10.00 200.00 % 100.00 603 n% x V
nMotor
P1.6.6
V/Hz curve
midpoint frequency
0.00 P1.6.4 Hz 60.00 604
P1.6.7
V/Hz curve
midpoint voltage
0.00 P1.6.5 % 100.00 605 n% x V
nMotor
Parameter max. value = par.
1.6.5
P1.6.8
Output voltage at
zero frequency
0.00 40.00 % 1.30 606 n% x V
nMotor
P1.6.9 Switching
frequency
1.0 Varies kHz Varies 601 See Table 8-12 on Page 8-57 for
exact values
P1.6.10
Overvoltage
controller
0 2 1 607 0 = Not used
1 = Used (no ramping)
2 = Used (ramping)
P1.6.11 Undervoltage
controller
0 1 1 608 0 = Not used
1 = Used