Firmware Manual

9000X AF Drives
7-18 For more information visit: www.eaton.com
MN04004001E
August 2010
Pump and Fan Control Application
Table 7-10: Output Signals, Digital Outputs — G1.3.1 (Continued)
Limit Settings (Control Keypad: Menu M1
G1.3.2)
Table 7-11: Output Signals, Limit Settings — G1.3.2
Code Parameter Min. Max. Unit Default Cust ID Note
P1.3.1.24
Fieldbus digital
input 1
DigOUT:0.1 DigOUT:E.10 DigOUT:0.1 455
P1.3.1.25
Fieldbus digital
input 2
DigOUT:0.1 DigOUT:E.10 DigOUT:0.1 456
P1.3.1.26
Fieldbus digital
input 3
DigOUT:0.1 DigOUT:E.10 DigOUT:0.1 457
P1.3.1.27
Autochange 1/
Aux 1 control
DigOUT:0.1 DigOUT:E.10 DigOUT:B.1 458
P1.3.1.28
Autochange 2/
Aux 2 control
DigOUT:0.1 DigOUT:E.10 DigOUT:B.2 459
P1.3.1.29
Autochange 3/
Aux 3 control
DigOUT:0.1 DigOUT:E.10 DigOUT:0.1 460
P1.3.1.30
Autochange 4/
Aux 4 control
DigOUT:0.1 DigOUT:E.10 DigOUT:0.1 461
P1.3.1.31
Autochange 5 DigOUT:0.1 DigOUT:E.10 DigOUT:0.1 462
Code Parameter Min. Max. Unit Default Cust ID Note
P1.3.2.1 Output frequency
limit 1 supervision
0 2 0 315 0 = No limit
1 = Low limit supervision
2 = High limit supervision
P1.3.2.2 Output freq. limit 1;
Supervised value
0.00 P1.1.2 Hz 0.00 316
P1.3.2.3 Output frequency
limit 2 supervision
0 2 0 346 0 = No limit
1 = Low limit supervision
2 = High limit supervision
P1.3.2.4 Output freq. limit 2;
Supervised value
0.00 P1.1.2 Hz 0.00 347
P1.3.2.5 Torque limit
supervision
0 2 0 348 0 = Not used
1 = Low limit supervision
2 = High limit supervision
P1.3.2.6 Torque limit
supervision value
0.0 300.0 % 100.0 349
P1.3.2.7 Reference limit
supervision
0 2 0 350 0 = Not used
1 = Low limit
2 = High limit
P1.3.2.8 Reference limit
supervision value
0.0 100.0 % 0.0 351
P1.3.2.9 External
brake-off delay
0.0 100.0 s 0.5 352
P1.3.2.10 External
brake-on delay
0.0 100.0 s 1.5 353
P1.3.2.11 FC temperature
supervision
0 2 0 354 0 = Not used
1 = Low limit
2 = High limit