Analog Input 3 (Control Keypad: Menu M1
G1.2.4)
Table 7-7: Input Signals, Analog Input 3 — G1.2.4
Remember to place jumpers of block X2 accordingly. See 9000X AF Drives User Manual, Chapter 4.
Analog Input 4. (Control Keypad: Menu M1
G1.2.5)
Table 7-8: Input Signals, Analog Input 4 — G1.2.5
Remember to place jumpers of block X2 accordingly. See 9000X AF Drives User Manual, Chapter 4.
Digital Inputs (Control Keypad: Menu M1
G1.2.6)
Table 7-9: Input Signals, Digital Inputs — G1.2.6
cc = closing contact; oc = opening contact.
Code Parameter Min. Max. Unit Default Cust ID Note
P1.2.4.1
AI3 signal selection AnIN:0.1 AnIN:E.10 AnIN:0.1 141
P1.2.4.2 AI3 filter time 0.00 10.00 s 0.10 142 0 = No filtering
P1.2.4.3 AI3 signal range 0 2 1 143 0 = 0 – 100%
1 = 4mA/20%–100%
2 = Custom range
P1.2.4.4 AI3 custom
minimum setting
-100.00 100.00 % 0.00 144
P1.2.4.5 AI3 custom
maximum setting
-100.00 100.00 % 100.00 145
P1.2.4.6 AI3 inversion 0 1 0 151 0 = Not inverted
1 = Inverted
Code Parameter Min. Max. Unit Default Cust ID Note
P1.2.5.1
AI4 signal selection AnIN:0.1 AnIN:E.10 AnIN:0.1 152
P1.2.5.2 AI4 filter time 0.00 10.00 s 0.10 153 0 = No filtering
P1.2.5.3 AI4 signal range 0 2 1 154 0 = 0 – 100%
1 = 4mA/20%–100%
2 = Custom range
P1.2.5.4 AI4 custom
minimum setting
-160.00 160.00 % 0.00 155
P1.2.5.5 AI4 custom
maximum setting
-160.00 160.00 % 100.00 156
P1.2.5.6 AI4 inversion 0 1 0 162 0 = Not inverted
1 = Inverted
Code Parameter Min. Max. Unit Default Cust ID Note
P1.2.6.1
Start A signal DigIN:01 DigIn:E.10 DigIN:A.1 423
P1.2.6.2
Start B signal DigIN:01 DigIn:E.10 DigIN:A.4 424
P1.2.6.3
Control place A/B
selection
DigIN:01 DigIn:E.10 DigIN:A.6 425 Control place A (oc)
Control place B (cc)
P1.2.6.4
External fault
(close)
DigIN:01 DigIn:E.10 DigIN:0.1 405 Ext. fault displayed (cc)
P1.2.6.5
External fault
(open)
DigIN:01 DigIn:E.10 DigIN:0.1 406 Ext. fault displayed (oc)
P1.2.6.6
Run enable DigIN:01 DigIn:E.10 DigIN:0.1 407 Motor start enabled (cc)
P1.2.6.7
Acc/Dec time
selection
DigIN:01 DigIn:E.10 DigIN:0.1 408 Acc/Dec time 1 (oc)