Firmware Manual
9000X AF Drives
7-14 For more information visit: www.eaton.com
MN04004001E
August 2010
Pump and Fan Control Application
Table 7-4: Input Signals, Basic Settings — G1.2.1 (Continued)
Analog Input 1 (Control Keypad: Menu M1
➔
G1.2.2)
Table 7-5: Input Signals, Analog Input 1 — G1.2.2
Remember to place jumpers of block X2 accordingly. See 9000X AF Drives User Manual, Chapter 4.
Analog Input 2 (Control Keypad: Menu M1
➔
G1.2.3)
Table 7-6: Input Signals, Analog Input 2 — G1.2.3
Remember to place jumpers of block X2 accordingly. See 9000X AF Drives User Manual, Chapter 4.
Code Parameter Min. Max. Unit Default Cust ID Note
P1.2.1.13 Motor
potentiometer
frequency reference
memory reset
0 2 1 367 0 = No reset
1 = Reset if stopped or powered
down
2 = Reset if powered down
P1.2.1.14 Motor
potentiometer PID
reference memory
reset
0 2 0 370 0 = No reset
1 = Reset if stopped or powered
down
2 = Reset if powered down
P1.2.1.15 B reference scale,
minimum
0.0 P1.2.1.16 Hz 0.0 344 0.0 = Scaling off
>0.0 = Scaled min. value
P1.2.1.16 B reference scale,
maximum
P1.2.1.15 320.0 Hz 0.0 345 0.0 = Scaling off
>0.0 = Scaled max. value
Code Parameter Min. Max. Unit Default Cust ID Note
P1.2.2.1
AI1 signal selection AnIN:A.1 AnIN:E.10 AnIN:A.1 377
P1.2.2.2 AI1 filter time 0.00 10.00 s 0.10 324 0 = No filtering
P1.2.2.3 AI1 signal range 0 2 0 320 0 = Signal range 0 – 100%
1 = Signal range 20 – 100%
2 = Custom range
P1.2.2.4 AI1 custom
minimum setting
-160.00 160.00 % 0.00 321
P1.2.2.5 AI1 custom
maximum setting
-160.00 160.00 % 100.00 322
P1.2.2.6 AI1 signal inversion 0.00 320.00 Hz 0.00 323 0 = Not inverted
1 = Inverted
Code Parameter Min. Max. Unit Default Cust ID Note
P1.2.3.1
AI2 signal selection AnIN:0.1 AnIN:E.10 AnIN:A.2 388
P1.2.3.2 AI2 filter time 0.00 10.00 s 0.10 329 0 = No filtering
P1.2.3.3 AI2 signal range 0 2 1 325 0 = 0–10V
1 = 4mA/20%–100%
2 = Custom range
P1.2.3.4 AI2 custom
minimum setting
-160.00 160.00 % 0.00 326
P1.2.3.5 AI2 custom
maximum setting
-160.00 160.00 % 100.00 327
P1.2.3.6 AI2 signal inversion 0.00 320.00 Hz 0.00 328 0 = Not inverted
1 = Inverted